AC service · Corrosion

Formicary corrosion in AC coils: causes, signs and prevention

Formicary or ant-nest corrosion is a network of microscopic tunnels in copper tubing that can cause pinhole leaks within weeks or months. It needs moisture, oxygen and weak organic acids such as formic and acetic acid. These come from sources like adhesives, building materials, some solvents and cleaners. Prevention means clean air, the right cleaners and protective coatings.

Also called
Ant-nest corrosion
Needs
Moisture + oxygen + organic acids
Sign
Pinhole leaks, discoloured copper
Help
Coil coating, correct cleaners

What causes it

The Institute of Corrosion explains that formicary corrosion needs three things at once: oxygen, moisture and weak organic acids. The usual acids are carboxylic acids such as formic, acetic, propionic and butyric acid [1]. Sources include coil manufacturing oils, cleaning solvents and degreasers, building materials, adhesives and disinfectants [1].

Signs

  • Leaks within weeks or months of installation.
  • Patches of discoloured copper: dull grey or black, red-brown or purple.
  • Pinhole leaks that are hard to see with the eye.

Prevention for technicians

  • Ask for the pH and acid content of any cleaner you use on coils, and avoid products that leave organic acid residues.
  • Rinse cleaners off as the label directs.
  • Keep the indoor unit away from fresh paint, adhesives and strong solvent vapour.
  • Apply a protective coil coating such as Aerosure Coil Saver after cleaning, in high-risk sites.

Products used

Quick answers

What causes formicary corrosion in AC coils?

Moisture and oxygen together with weak organic acids such as formic and acetic acid, which come from sources such as adhesives, building materials, some solvents and cleaners.

What causes formicary corrosion?

Weak organic acids, mainly formic and acetic acid from indoor sources such as some adhesives, cleaners and building materials, attack thin copper tubes and leave tiny pinholes. The Institute of Corrosion describes the ant-nest pattern.

How do I protect coils against it?

Keep coils clean, avoid acidic or unsuitable cleaners on copper, and use a protective coil coating on sites with known corrosion problems.

Sources

  1. Institute of Corrosion: Recognising hidden formicary (ant nest) corrosion

Stock Aerosure for your service team

Trade pricing for technicians, AMC companies and distributors. We reply within one working day.

AC maintenance numbers to know

Published guidance for room ACs. Follow the AC maker’s manual and the product label.
WhatTypical range
Clean or replace filtersEvery 1 to 2 months in the cooling season, sooner in dust [source]
Energy saved by a clean filter5% to 15% less energy than with a clogged filter [source]
Check the indoor (evaporator) coilEvery 12 months; clean when dirty [source]
Drain lineClear it at each service so water cannot back up [source]
Star labelCompare models by BEE star rating and ISEER [source]

What are the signs an AC needs a service?

  • Weak or uneven airflow from the indoor unit.
  • A musty or sour smell when the AC starts.
  • Water dripping from the indoor unit or a full drain tray.
  • Ice on the indoor coil or the copper pipes.
  • The AC runs longer to reach the set temperature, or bills go up.
  • New rattles, hissing or buzzing from either unit.

What should be in your service kit?

  • Gloves and eye protection
  • Coil foam cleaner and a spray bottle of clean water for rinsing
  • Soft brush or vacuum for loose dust
  • Fin comb for bent fins
  • Drain bag or sheet to catch runoff
  • Wire or blower to clear the drain line
  • Torch, screwdriver set and a way to confirm the power is isolated

Carry the product SDS on your phone and follow the AC maker’s manual for the unit you are servicing.